Panasonic ideas for life Global
Search Panasonic Global Site

Business

Global Home Business > Eco Solutions > Air Conditioning and Purification > Heatexchange Unit > Energy Recovery ventilator

Heatexchange Unit

Energy(Heat) Recovery Ventilator

Panasonic Energy recovery ventilator can reduce the outside air load because they efficiently recover the heat lost by ventilation during the heat recovery process. This results in energy-saving ventilation and lower running costs for air-conditioner and heating equipment.

Energy recovery ventilatorheat exchange elements

Feature

  1. Energy saving ventilation:
    Energy consumption is dramatically reduced by using an counter-flow heat exchange elements. The air conditioning load is reduced by about 20%, resulting in significant energy saving
  2. Slim design:
    A slim shape saves on installation works: Compared with the cross flow configuration, the counter-flow elements is more compact and slim.
  3. Structure:
    The counter-flow heat exchanger elements requires no regular cleaning.
  4. Quiet operation:
    Low noise operation results in noticeably quieter unit.
  5. Product Range Air Volume:
    250cmh, 350cmh, 500cmh, 800cmh, 1000cmh in total 5 models
    Enthalpy exchange efficiency: at Cooling( from62% to 69%), at Heating( from from 67% to 74%)

Dramatic energy saving achieved through adoption of a high-efficiency counter-flow heat-exchange element.

  1. Building apartment (Each floor independently air-conditioned)
  2. Area of middle floor: 80m2
  3. Indoor load:summer, winter and autumn 80m2 x 120kcal/hm2 x 4.2=40,320kj/h-(1)
  4. Room temp&Humidity
    Room temp Cooling 26degreeC(RH50%) ,Heating 20degreeC(RH50% Outside Temp 33degreeC(RH63%), Heating 0degree C(RH63%)
  5. 1000 hours od operation in each season
  6. Ventilation rate: 20x80/3=533=500m3/h
  7. Ventilation load when a ventilation fans is used during cooling 500x7.6kcal/kgx1.2x4.2=19,150kj/h-(2)
  8. Ventilation load when energy recovery ventilation is used during cooling 500x7.6kcal/kgx(1-0.62)x1.2x4.2=7,280kj/h-(3)
    Application Example= How much we can save energy

save energy

Typical System Links to a Package Air Conditioner:
Typical System