Main Contents begins from here.
Heatexchange Unit
|
| Custom-made development to suit your base station environment (customer specifications) |
| |
 |
| |
TYPE-1 |
TYPE-2 |
TYPE-3 |
TYPE-4 |
| TYPE |
 |
 |
 |
 |
Heat
exchange
element |
 |
 |
 |
 |
|
Standard design specifications
| Type |
TYPE-1 |
TYPE-2 |
TYPE-3 |
TYPE-4 |
| Cooling capacity |
28W/K |
85W/K |
180W/K |
250W/K |
Dimensions
(mm) |
W |
420 |
625 |
600 |
1050 |
| H |
605 |
920 |
1360 |
1250 |
| D |
200 |
330 |
250 |
250 |
| Weight (kg) |
11 |
40 |
40 |
70 |
| Noise (dB(A)) |
40 |
39.5 |
60 |
60 |
| Power supply voltage (V) |
DC24,48 or AC110-240 |
| Power consumption (W) |
35 |
68 |
350 |
600 |
|
|
|
* The above models and figures are just examples of custom-made developments.
Actual products will be determined according to customer's requirements. |
|
■ Fan: The best possible type of fan, whether it be a turbo type or sirocco type, is selected and mounted according to the customer's individual specifications and requirements. The best choice from steel, aluminum, or resin is selected.
■ Motor: A brushless-type, high-efficiency DC motor is adopted. The control voltage is either 24 V or 48 V. AC motors can also be supplied.
Heat exchange element: Made of resin (sensible heat exchange)
■ Heater: To be provided according to customer specifications
■ Heat load: 400 to 4,000 W
■ Cooling capacity: 20 W/K to 250 W/K
■ Control: To be supported according to customer' requirements
■ Product safety standard: Our design policy is to meet the customer' specific requirements for specifications. We will also acquire certification as necessary to meet local safety regulations and standards.
(e.g.: UL, CE, NEMA, GR487, IP55) |
Application
Cooling unit (climate unit) for cellular phone radio base station
Cooling unit for FTTH (Fiber to the flame) base station |